Cisco Nexus
7000 has gain popularity in the past year. Given its size, there is always a
question regarding the type of rack needed to house the switch especially for
those who are the first-time installer. In this article, I will provide quick
tips on how to choose a rack for a Cisco Nexus 7K, specifically for Nexus 7010
and 7018, as well as some ideas for PDU selection. Obviously, there are many
manufacturers that you can choose from so the article will present in a
vendor-neutral fashion.
Nexus
7010
Below is the diagram from Cisco
documentation. The depth of the chassis including the front cable management
is 38 inches. Cisco recommends front-to-back racking space of 46 inches. So the
options are the followings in order of preference.
For 4-Post
rack
1. In my
opinion, if there is no compelling reason to have the chassis in a cabinet, this
is a preferred option for the reason being that the front and back are open.
Although you should still ensure the front and back clearance, you have more
flexibility and do not need to worry about the chassis not being to fit into a
cabinet. Cisco requires the depth of at least 24 inch (610mm) for the mounting
bracket. You will also be better off with a bottom horizontal PDU unless you can
somehow manage to install vertical
ones.
For cabinet-style
rack
1. A
rack with 47-inch (1200mm) or deeper and adjustable mounting rail, as you will
need to move the front rail back a few inches to accommodate the cable
management on the Nexus is a recommended cabinet option. You will have enough
rear space for vertical PDUs (as permitted by the cabinet) and cabling. You
should also be able to close both front and back
doors.
2. A rack
with 42 to 47 inch (1070-1200mm) in depth and adjustable mounting rail will
leave you minimal rear space for cabling, and most likely prohibit the use of
vertical PDU. In this case, bottom horizontal PDUs would work best. You should
still be able to close the door but this depends on space left in the
rack.
3. Any rack
with less than 42 inch (1070mm) in depth will most likely not be able to
accommodate the chassis unless you plan to leave the back of cabinet open and
have cables hanging outside. I would advise against this
option.
Nexus
7018
Below is the diagram from Cisco
documentation. You can see the physical chassis width and depth remain the
same as 7010 so our previous discussion on the depth of the rack still applies.
However, there is now a requirement for side clearances as the 7018 has
side-to-side airflow.
For 4-Post
rack
1. Again, in my opinion, this is the prefer option. In addition to previous
discussion, you will need to leave enough space of at least 11 inch (280mm) on
each side especially if the adjacent rack is also a
7018.
For
cabinet-style
rack
1. Unless you can get an extra wide rack to
accommodate airflow, you will most likely need to remove the side panels and
leave at least 11 inch (280mm) to adjacent racks,
Tips on
PDU:
In
most cases, horizontal PDUs are the best option but vertical PDUs also work fine
as long as there is extra room to securely mount them in the cabinet without
interfering with the chassis. Some rack vendor design their rack to specifically
accommodate their vertical PDUs. Each Nexus power supply has two power inputs so
you may need up to six outlets (three power supplies) for 7010 or 8 outlets
(four power supplies) for
7018.
For
example, given power sources are two three-phase circuits, you can buy two
three-phase PDUs with at least six C-19 outlets each and connect the power
supplies to them such that if one circuit fails, all power supplies continue to
function using the other circuit (ie. grid redundancy). This will result in 2:1
power share but should work fine in most cases.
Other
Tips:
- Some PDUs, three-phase in particular, have very thick power cord and
large connector. They might have trouble getting through a hole, either top or
bottom, to exit the cabinet. In which case, you will have trouble closing the
back door.
- For
a 4-post rack, install vertical cable managements on both
sides
- Although
you may think the majority of cables are at the front and there is no need for
back space, the power cords at the back will need a few inches themselves so it
is always wise to have some back space.
Check
List:
1. Choose proper racks per guide
above
2. Know the
type of power source (ie. Single-Phase,
Three-Phase)
3. Ensure sufficient quantity of power
source
4. Choose proper PDUs (ie. vertical VS horizontal, input/output power,
quantity of outlets, type of connectors) and sufficient quantity of
outlets
5. Make
sure the power cords ordered with the Nexus are compatible with the PDU (eg.
NEMA L6-20, L6-30, C19/C20 etc.)
Conclusion:
To ensure that your Nexus 7000 installation goes smoothly, it is important to do
all the due diligences on the rack and PDU selections as well as knowing your
power source and connector types.
Additional
Resources:
Cisco
Nexus 7000 Series Site Preparation Guide
Cisco
Nexus 7000 Series Hardware Installation and Reference
Guide
Cisco
Nexus 7000 Series Power Supply Modules
Author: Metha Chiewanichakorn , CCIE#23585
(R&S/Security/Service Provider)

Great post!
Thanks for this.